規格
|
額定風量(m3/h)
|
額(é)定供冷量(liàng)(kW)
|
額定供熱量(liàng)(kW)
|
|
FP-34
|
340
|
1.80
|
2.70
|
|
FP-51
|
510
|
2.70
|
4.05
|
|
FP-68
|
680
|
3.60
|
5.40
|
|
FP-85
|
850
|
4.50
|
6.75
|
|
FP-102
|
1020
|
5.40
|
8.10
|
|
FP-136
|
1360
|
7.20
|
10.80
|
|
FP-170
|
1700
|
9.00
|
13.50 |
|
FP-204
|
2040
|
10.80
|
16.20
|
|
FP-238
|
2380
|
12.60
|
18.90
|
基本規格參數表
|
規(guī)格
|
額定風量(m3/h)
|
輸入功率(lǜ)(W)
|
噪聲[dB(A)]
|
水阻(kPa)
|
||||
|
低靜壓機組
|
高靜壓機組
|
低靜壓機組
|
高(gāo)靜壓機組
|
|||||
|
30Pa
|
50Pa
|
30Pa
|
50Pa
|
|||||
|
FP-34
|
340
|
37
|
44
|
49
|
37
|
40
|
42
|
30
|
|
FP-51
|
510
|
52
|
59
|
66
|
39
|
42
|
44
|
30
|
|
FP-68
|
680
|
62
|
72
|
84
|
41
|
44
|
46
|
30
|
|
FP-85
|
850
|
76
|
87
|
100
|
43
|
46
|
47
|
30
|
|
FP-102
|
1020
|
96
|
108
|
118
|
45
|
47
|
49
|
40
|
|
FP-136
|
1360
|
134
|
156
|
174
|
46
|
48
|
50
|
40
|
|
FP-170
|
1700
|
152
|
174
|
210
|
48
|
50
|
52
|
40
|
|
FP-204
|
2040
|
189
|
212
|
250
|
50
|
52
|
54
|
40
|
|
FP-238
|
2380
|
228
|
253
|
300
|
52
|
54
|
56
|
50
|
5. 在選用機組時,應考慮實際性(xìng)能(néng)與額定值(zhí)的(de)偏差,並注意以下(xià)特點:
1) 機組額定(dìng)供(gòng)冷量一般為在空氣焓降值等於15.9kJ/kg 條件下的測試值;
2) 單盤管機(jī)組額定供熱量一(yī)般為額(é)定供冷量的1.5 倍;
3) 額定值各項參數均為風機在高轉速下的值,設(shè)計(jì)時一般宜按產品樣本的中(zhōng)檔風速(sù)下的數(shù)值選用(yòng)。若產品未提供不同風速下的額(é)定值數據,可參照表3進(jìn)行換算。
表3 風量換算係數(shù).
|
額(é)定值類別
|
高風速
|
中風速
|
低風速
|
|
風量
|
1
|
0.75
|
0.50
|
注意事項
施工、安裝要點
1. 機組供(gòng)水(shuǐ)入口處,應裝設過濾(lǜ)器。在衝洗冷媒水係統幹(gàn)管時,汙水不準通過(guò)盤管。盤管接(jiē)管的高點應設(shè)排氣裝置,低點應設泄水裝置。
2. 風(fēng)機盤管機組的冷凝水排出管必須有一定的坡度,應保證滴(dī)水盤中不積水。
3. 風機盤管機組的安裝可參見(jiàn)建築標準設計圖集01K403《風機盤管安裝》。
執行標準
產品標準
GB/T19232-2003《風機盤管機組(zǔ)》
工程標準
GB50243-2002《通風(fēng)與空調工程(chéng)施工質量驗收規範》
服務電話:18263083083
山東神马影院(míng)空調設備有限公司
微信二維碼
山東神马影院空調設備Copyright © 2023 山東神马影院空(kōng)調設備有限公司 版權所有 備案號